Wire-bending space
Minimum space for deflection of conductions at terminals, and minimum width of gutters & wireways
Pull box, jbox, and wireway dimensions
Minimum dimensions for boxes, wireways, & gutters that:
-
Contain conductors of 4 AWG & larger and
-
Utilize angle pulls or splices
NEC Article References
Article 312: Cabinets, Cutout Boxes, and Meter Socket Enclosures
312.6
Deflection of conductors
NEC 2023
Table 312.6(A)
Table 312.6(B)(2)
Article 314: Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings
314.28
Pull and junction boxes and conduit bodies
NEC 2023
314.28(A)(2)
314.28(A)(2) Exception
Article 376: Metal Wireways
376.23
Insulated Conductors
NEC 2023
376.23(A)
376.23(B)